Used in hazardous area locations, sealing fittings help to seal off and prevent vapors, gases, etc. from passing from one section of a conduit system to another.

The EYS sealing fittings hold the following ratings:

- CL I, DIV 1 & 2, Groups A, B, C, D
- CL II, DIV 1 & 2; , Groups E, F, G
- CL III
(when used with Crouse-Hinds Chico A and Chico X product)

Material:
-Body: CF8M (316 SS)
-Plug: 316 SS
Compliances: UL Listed for Canada and US (UL Standard 1203)
UL File Number EBNV.E472023
Canada UL File Number EBNV7.E472023

100% Made in USA



EYS
Unit of Measure
Items EYS_Photo
EYS75
3/4" Conduit Sealing Fitting
EYS_Photo
EYS100
1" Conduit Sealing Fitting
Size N/A 3/4 in. N/A 1 in.
Dimension A N/A 3/4-14 NPT N/A 1-11-1/2 NPT
Dimension B N/A 1.50 in N/A 1.75 in
Dimension C N/A 1.97 in N/A 2.22 in
Dimension D N/A 3.63 in N/A 4.25 in
Dimension E N/A 3/4-14 NPT N/A 1-11-1/2 NPT
Dimension F N/A 1/4-18 NPT